SOLA 4000 - Operating Panel
LED 18
LOAD FED BY BYPASS POWER SUPPLY
Yellow LED is continually illuminated = Load fed by static
bypass
Otherwise LED is off.
LED 19
LOAD IS SUPPLIED
Green LED is continually illuminated = Load fed either by
inverter or by static bypass and IUG is closed
Otherwise LED is off.
LED 27
BATTERY TEST
This test is only performed if the batteries are fully charged. Other-
wise the test is skipped and performed in the following month.
LED off = BATTERY TEST function not active
Green LED is continually illuminated = BATTERY TEST func-
tion activated, but UPS is not performing the test
Green LED flashing slowly = BATTERY TEST running
Red LED flashing fast + BUZZER beeping fast = BATTERY
TEST failed. Test battery capacity.
LED 28
E.P.O.
Red LED is continually illuminated = E.P.O. has been activated
Note: For parallel and hot-standby systems, EPO may be have
been activated at any unit.
LED 26
STATIC SWITCH
Green LED continually illuminated = Bypass available
Green LED flashing = Bypass not synchronised but the mains
is OK
LED off = Mains not OK
LEDs
BATTERY INDICATOR
a) During the charging phase (green LED L5 ON)
Green LEDs continuously illuminated indicate the actual battery
autonomy as a percentage of the nominal battery autonomy,
depending on the actual load and battery charging status.
b) During the discharging phase (yellow LED 4 ON)
If, during the discharging phase, the actual battery autonomy
goes below 20% autonomy, the system signals the alarm "Low
Battery ".
- The BUZZER beeps continually.
- The colour of the "battery indicator" LEDs changes from green to
red.
The actual autonomy is signalled by the flashing of the corre-
sponding LED.
When the LED corresponding to 0% autonomy starts flashing:
- The buzzer beeps continually and cannot be muted.
- The inverter will cease to operate soon.