Powerware SOLA 4000 Network Card User Manual


 
JUE 401267
86
SOLA 4000 - Operating Panel
4 PANEL SETTINGS
4.1 DIP Switch Settings
With the DIP switches SW1 and SW2 on the CPU/NCP pcb inside
the front door , the operating parameters can be set according to
actual conditions.
Note: The following settings apply only with the software V2.0 or
later.
DIP Switch SW1
Dip 1 Dip 2 Dip 3 Dip 4
UPS RATING
(KVA)
OFF OFF OFF OFF 10
ON OFF OFF OFF 15
OFF ON OFF OFF 20
ON ON OFF OFF 30
OFF OFF ON OFF 40
ON OFF ON OFF 60
OFF ON ON OFF 80
ON ON ON OFF 100
OFF OFF OFF ON 120
TAB. 4.1 - Setting of SW1 - UPS rating
DIP Switch SW1
Nominal Voltage
DIP 7 DIP 8 Vnom
OFF OFF 120
ON OFF 220
OFF ON 230
ON ON 240
TAB. 4.2 - Setting of SW1
TAB. 4.3 - Setting of SW1
Nominal Voltage
DIP Switch SW1
DIP 5 CONFIGURATION
OFF Not Hot-standby
ON Hot-Standby
DIP 6 BYPASS - LINE
OFF Installed
ON Not installed
4 Panel Settings