Bosch Appliances D6100 Network Router User Manual


 
Conettix D6600/D6100 | Computer Interface Manual | Appendix C: Modem IIIa2 Messages
106 Bosch Security Systems, Inc. | 1/07 | 4998122703-01
Table 92: Modem IIIa
2
Messages (continued)
Event Device/Mode Display Explanation Refer to Section
C.1 Zonex and
Comex
Translation on
page 137.
527.
Point Bus
Restoral
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaa RESTORAL ZN D
h1rrlssssssaaaasRsssDt
<header>[#aaaa|NURD]
Zonex restoral
message: indicates a
trouble condition on
the wiring from the
POPEX Module to the
POPITs was cleared.
Wiring connecting the
control panel and
keypads restored. Point
bus, supervised
keypad, printer, or
other serial device was
restored.
2.
528.
Point Bus
Restoral
(area reported)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa PT BUS RESTORAL
+++ACC aaaa AREA=aa
h1rrlssssssaaaasRsssDt
<header>[#aaaa|NriaaER]
529.
Point Bypass
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa POINT BYPASS
+++ ACC aaaa AREA=a POINT=ppp ID=iii
h1rrlssssssaaaasNspppt
<header>[#aaaa|Nria/idiiiUBppp]
The POINT in the
AREA specified in the
second line of the
report is faulted, and
was bypassed by the
user with the specified
ID.
1,
D7112
530.
Point Bypass
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z
h1rrlssssssaaaasTssszt
<header>[#aaaa|NBTz]
9,
D7112
531.
Point Bypass
(Area and ID
Not Reported)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa POINT BYPASS
+++ ACC aaaa POINT=ppp
h1rrlssssssaaaasNspppt
<header>[#aaaa|NUBppp]
The POINT in the
AREA specified in the
second line of the
report is faulted, and
was bypassed by the
user with the specified
ID.
532.
Point Bypass
(ID not
reported)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa POINT BYPASS
+++ ACC aaaa AREA=a POINT=ppp
h1rrlssssssaaaasNspppt
<header>[#aaaa|NriaUBppp]
The POINT in the
AREA specified in the
second line of the
report is faulted, and
was bypassed by the
user with the specified
ID.
1,
D7112
533.
Point Bypass
(point < 255)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa POINT BYPASS
+++ACC aaaa AREA=a POINT=ppp
h1rrlssssssaaaasNspppt
<header>[#aaaa|NriaUBppp]
534.
Point Bypass
(point < 255)
(fire point)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa POINT BYPASS
+++ACC aaaa FIRE POINT
+++ACC aaaa AREA=a POINT=ppp
h1rrlssssssaaaasNspppt
<header>[#aaaa|NriaFBppp]
535.
Point Bypass
(point > 254)
(fire point)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa POINT BYPASS
+++ACC aaaa FIRE POINT
+++ACC aaaa AREA=a POINT=pppp
h1rrlssssssaaaasNppppt
<header>[#aaaa|NriaaFBpppp]
536.
Point Bypass
(point < 255)
(supervisory
point)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa POINT BYPASS
+++ACC aaaa SUPERVISORY POINT
+++ACC aaaa AREA=a POINT=ppp
h1rrlssssssaaaasNspppt
<header>[#aaaa|NriaSBppp]