Appendix C: Modem IIIa
2
Messages
For lines that are grouped, Gxx appears instead of Lxx.
Table 92: Modem IIIa
2
Messages
Event Device/Mode Display Explanation Refer to Section
C.1 Zonex and
Comex
Translation on
page 137.
1. Abort
(User not
identified)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa ABORT BY USER
+++ACC aaaa AREA=a
h1rrlssssssaaaasIsD41t
<header>[#aaaa|NriaAB]
2.
Abort
(users < 255)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa ABORT BY USER
+++ACC aaaa AREA=a ID=iii
h1rrlssssssaaaasIsiiit
<header>[#aaaa|Nria/idiiiAB]
3.
Abort
(users > 254)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa ABORT BY USER
+++ACC aaaa AREA=aa ID=iiii
h1rrlssssssaaaasIiiiit
<header>[#aaaa|Nriaa/idiiiiAB]
4.
Access
Granted
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa ACCESS GRANTED
+++ ACC aaaa AREA=a CRD=iii-x POINT=ppp
h1rrlssssssaaaaAGspppt
<header>[#aaaa|Nria/idiiiDGppp] or
<header>[#aaaa|Nria/idiii/ssxDGppp]
5.
Access
Granted
(point < 255,
user > 254)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa ACCESS GRANTED
+++ACC aaaa AREA=aa CRD=iiii POINT=ppp
h1rrlssssssaaaaAGspppt
<header>[#aaaa|Nria/idiiiiDGppp]
6.
Access
Granted
(point > 254,
user < 255)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa ACCESS GRANTED
+++ACC aaaa AREA=aa CRD=iii-x POINT=pppp
h1rrlssssssaaaaAGppppt
<header>[#aaaa|Nriaa/idiiiDGpppp] or
<header>[#aaaa|Nriaa/idiii/ssxDGpppp]
7.
Access
Granted
(point > 254,
user > 255)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa ACCESS GRANTED
+++ACC aaaa AREA=aa CRD=iiii POINT=pppp
h1rrlssssssaaaaAGppppt
<header>[#aaaa|Nriaa/idiiiiDGpppp]
8.
AC Fail
(Area
reported)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa AC FAILURE
+++ACC aaaa AREA=aa
h1rrlssssssaaaasPsssst
<header>[#aaaa|NriaaAT]
9.
AC Fail
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa AC FAILURE
h1rrlssssssaaaasPsssst
<header>[#aaaa|NAT]
No AC power. Control
panel is running on
battery power only.
You can program the
control panel to defer
this report.
10.
AC Fail
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaa TROUBLE ZN z
h1rrlssssssaaaasTssszt
<header>[#aaaa|NATO]
2,
z = 0
11.
AC Fail
(as a rider)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaa AC FAILED
h1rrlssssssaaaasPsssst
<header>[#aaaa|NAT]
No AC power. Control
anel is running on
battery power only.
This report is sent
along with the next
report transmitted - it
is not transmitted
independently.
2,