3.2.3 Ademco 4-1 Express (Message Type b)
SIA Mode Description 4-1 Express
Example
<LF><CRC><b><sequence#><receiver#><line#>[#aaaa|X]<CR>
Table 41: Ademco 4-1 Express (Message Type b) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
b
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits are 01 to 99 for the
D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits are 00
to 99. The receiver uses Line 0 (zero) for internal messages.
account#
The communicator's account number has four digits.
X
Zone number
Figure 9: Message sent to printer
mm/ddshh:mmsLxxsE41sACCTsaaaasEVENT=X
For lines that are grouped, Gxx appears
instead of Lxx.
Table 42: Ademco 4-1 Express (Message
Type b) Printer Output
Characters Description
E41 Ademco 4-1 Express format.
Lxx: Line number.
Gxx Grouped line numbers.