Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
.
Bosch Security Systems, Inc. | 1/07 | 4998122703-01 29
3.2.2 Ademco Contact-ID (Message Type a)
SIA Mode Description Contact-ID
Example
<LF><CRC><a><sequence#><receiver#><line#>[#aaaa|18QXYZGGCCC]<CR>
Table 39: Ademco Contact-ID (Message Type a) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
a
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits are 01 to 99 for the
D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits are 00
to 99. The receiver uses Line 0 (zero) for internal messages.
account#
The communicator's account number has four digits.
18
Ademco Contact-ID format number.
Q
Qualifier, 1 = New event or opening, 3 = New restore or closing, 6 = Previous event.
XYZ
Class code and event code (refer to Appendix A: Contact ID Event Code Classifications on
page 53).
GG
Group number.
CCC
Zone codes or User ID.
Figure 8: Message sent to printer
mm/ddshh:mmsLxxsCIDsACCTsaaaa+++sACCsa
aaasNNNsEVENT=XYZsG=GGsC=CCC
For lines that are grouped, Gxx appears
instead of Lxx.
Table 40: Ademco Contact-ID (Message Type a)
Printer Output
Characters Description
CID Contact-ID format.
Gxx Grouped Line numbers.
Lxx Line number.
NNN If Q = 1, print E/O for new event or
opening If Q = 3, print R/C for restore or
closing If Q = 6, print “OLD” for old
messages and events.