Bosch Appliances D6100 Network Router User Manual


 
Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
12 Bosch Security Systems, Inc. | 1/07 | 4998122703-01
3.1.6 ADT SIA (Message Type S)
D6500 Byte Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
h S r r l [ # a a a a | d a m m - d d - y
22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42
ADT SIA
Example
y t I h h : m m : s s E M M Z Z Z Z /
**
*
t
Table 8: ADT SIA (Message Type S) Byte Description
# Title Description
1 Header Character (h)
Optional. Check with the computer automation software for compatibility.
2 Message Type
S
3-4 Receiver Number
Receiver gateway number from 01 to 99.
5 Line/Group Number
Line number in the receiver gateway that sent the message.
6 space
One space.
7 #
#
8-11 Account Number
Up to sixteen digits in the account number.
12 |
Separator. Indicates more data positions after account number.
13-32 Date and Time
Date and time.
33 E
SIA block code.
34-35 Event Code
SIA event code (refer to Appendix G ADT SIA Report Codes on page 149).
36-39 Zone
Zone number.
40 /
Separator.
41 ***
Next block of data.
42 Trailer Character
Typically, this is HEX 14.
3.1.7 Caller ID (Message Type e)
D6500 Byte Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22
Caller ID
Example
h e r r 1 T T T T T T T T T T T T T T T T t
Table 9: Caller ID (Message Type e) Byte Description
# Title Description
1 Header Character (h)
Optional. Check with the computer automation software for compatibility.
2 Message Type
e
3-4 Receiver Number
Receiver gateway Number from 01 to 99.
5 Line/Group Number
Line number in the receiver gateway that sent the message.
6-21 Caller ID
Up to sixteen digits, Caller ID with less than sixteen characters is right aligned with
leading ASCII spaces.
22 Trailer Character
Typically, this is HEX 14.