Bosch Appliances D6100 Network Router User Manual


 
Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
46 Bosch Security Systems, Inc. | 1/07 | 4998122703-01
Table 77: Silent Knight FSK1 Optional Outputs (continued)
Report Code Description To Automation Note
90 Opening OP00 90
91 to 99 Opening 01 to 09 OP0x 91 to 99
3.2.24 Silent Knight FSK2 (Message Type m)
SIA Mode Description Silent Knight
FSK2 Example
<LF><CRC><m><sequence#><receiver#><line#>[#aaaaaa|
EEZZ”ECZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ]<CR>
Table 78: Silent Knight FSK2 (Message Type m) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
m
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to
99. The receiver uses Line 0 (zero) for internal messages.
account #
The communicator's account number has up to six digits.
EEZZ”EEZZ”EEZZ”EEZZ”
EEZZ”EEZZ”EEZZ”EEZZ
Up to eight reports. One report has four digits: one-digit event code, one-digit condition code,
and two-digit zone code. The quote (“) is the separation character.