Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
44 Bosch Security Systems, Inc. | 1/07 | 4998122703-01
3.2.22 Silent Knight FSK() (Message Type <TAB>)
SIA Mode Description Silent Knight
FSK0 Example
<LF><CRC><TAB><sequence#><receiver#><line#>[#aaaa|data]<CR>
Table 74: Silent Knight FSK0 (Message Type <TAB>) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
<TAB>
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to
99. The receiver uses Line 0 (zero) for internal messages.
account #
The communicator's account number has four digits.
Data
Data.
3.2.23 Silent Knight FSK1 (Message Type m)
SIA Mode Description Silent Knight
FSK1 Example
<LF><CRC><m><sequence#><receiver#><line#>[#aaaa|
EEZZ”ECZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ”EEZZ]<CR>
Table 75: Silent Knight FSK1 (Message Type m) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
m
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to
99. The receiver uses Line 0 (zero) for internal messages.
account #
The communicator's account number has four digits.
EEZZ”EEZZ”EEZZ”EEZZ”
EEZZ”EEZZ”EEZZ”EEZZ
Up to eight reports. One report has four digits: one-digit event code, one-digit condition code,
and two-digit zone code. The quote (“) is the separation character.