Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
.
Bosch Security Systems, Inc. | 1/07 | 4998122703-01 49
3.2.28 Varitech FSK 4-2 (Message Type <TAB>)
SIA Mode Description Varitech FSK 4-2
Example
<LF><CRC><TAB><sequence#><receiver#><line#>[#aaaa|data]<CR>
Table 83: Varitech FSK 4-2 (Message Type <TAB>) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message
<TAB>
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to
99. The receiver uses Line 0 (zero) for internal messages.
account #
The communicator's account number has four digits.
data
The event type and two-digit zone number.
3.2.29 VONK (Message Type V)
SIA Mode Description VONK Example
<LF><CRC><V><sequence#><receiver#><line#>[#aa|123456789ABCDEFG]<CR>
Table 84: VONK (Message Type V) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
V
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to
99. The receiver uses Line 0 (zero) for internal messages.
account #
The communicator's account number has two digits.
Data
Status of zones 1 to 16. If the zone is closed, a “.” (Period) appears in this position. If the zone
is open, any digit from 1 to G appears in this position.