Bosch Appliances D6100 Network Router User Manual


 
Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
50 Bosch Security Systems, Inc. | 1/07 | 4998122703-01
3.2.30 X-SIA text (Message Type <TAB>)
SIA Mode Description X-SIA Example
<LF><CRC><TAB><sequence#><receiver#><line#>[#aaaa|EMMZZZZ*'TTTTTTTTTTTTT'
NM/***]<CR>
Table 85: X-SIA text (Message Type <TAB>) Byte Description
Title Description
LF
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
<TAB>
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits: 01 to 99 for D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits: 00 to
99. The receiver uses Line 0 (zero) for internal messages.
account #
The communicator's account number has up to 16 digits.
E
SIA block code.
MM
SIA event code.
ZZZZ
Zone number.
*
Text identifier.
`
Single quote.
TT…TTT
13 character text string.
Single quote.
NM
Unit field characters.
/
Separator.
***
Next data.
Figure 23: Message sent to printer
MM/DDsHH:MMsLxxsSIAsACCTsAAAA+++sEMMZZ
ZZ*'TTTTTTTTTTTTT'NM+++sEMMZZZZ*'TTTTT
TTTTTTTT'NM
Table 86: X-SIA Printer/LCD output
Characters Description
MM/DDsHH:MM Date and time.
Lxx Line number.
SIA SIA format.
AAAA Account code.
E SIA block code.
MM SIA event code.
ZZZZ Zone number.
* Text identifier.
Single quote.
TTT…T 13 character text string.
Single quote.
NM Unit field characters.