Appendix A: Contact ID Event Code Classifications
Figure 24: Contact ID format
1234 E 123 01 123
1 2 3 4 5
1 - Customer (Subscriber Account Number)
2 - Event Qualifier - E = New Event, R = Restore
3 - Event Code - refer to Section A1 Event Codes
4 - Partition Number, 00 to 08 (always 00 for non-
partitioned panels)
5 - Zone ID number* - reporting the alarm (001 to
999) or user number for open or close reports.
* System status messages, such as AC Loss and
Low Battery, are Zone ID 000.
Table 90: Event Codes
# Event Type Zone
Medical:
100 Medical Emerg-Personal Emergency-#
101
Pendant
Transmitter
Emerg-Personal Emergency-#
102 Fail to report in Emerg-Fail to check in-#
Fire Alarms:
110 Fire Fire-Fire Alarm-#
111
Smoke
w/Verification
Fire-Fire Alarm-#
112 Combustion Fire-Combustion-#
113 Waterflow Fire-Water Flow-#
114 Heat Fire-Heat Sensor-#
115 Pull Station Fire-Pull Station-#
116 Duct Fire-Duct Sensor-#
117 Flame Fire-Flame Sensor-#
118 Near Alarm Fire-Near Alarm-#
Panic Alarms:
120 Panic Alarm Panic-Panic-#
121 Duress Panic-Duress-User #
122 Silent Panic-Silent Panic-#
123 Audible Panic-Audible Panic-#
124
Duress-Access
Granted
Panic-Duress Access Grant-#
125
Duress-Egress
Granted
Panic-Duress Egress Grant-#
Table 90: Event Codes (continued)
# Event Type Zone
Burglar Alarms:
130 Burglary Burg-Burglary-#
131 Perimeter Burg-Perimeter-#
132 Interior Burg-Interior-#
133 24 HR Burg (Aux) Burg-24 Hour-#
134 Entry/Exit Burg-Entry/Exit-#
135 Day/Night Burg-Day/Night-#
136 Outdoor Burg-Outdoor-#
137 Tamper Burg-Tamper-#
138 Near Alarm Burg-Near Alarm-#
139 Intrusion Verifier Burg-Intrusion Verifier-#
General Alarms:
140 General Alarm Alarm-General Alarm-#
141
Polling Loop
Open
Alarm-Polling Loop Open
142
Polling Loop
Short (AL)
Alarm-Polling Loop Short
143
Expansion Mod
Failure
Alarm-Exp. Module Tamper-#
144 Sensor Tamper Alarm-Sensor Tamper-#
145
Expansion Module
Tamper
Alarm-Exp. Module Tamper-#
146 Silent Burg Alarm-Silent Burglary-#