Bosch Appliances D6100 Network Router User Manual


 
Conettix D6600/D6100 | Computer Interface Manual | Appendix C: Modem IIIa2 Messages
86 Bosch Security Systems, Inc. | 1/07 | 4998122703-01
Table 92: Modem IIIa
2
Messages (continued)
Event Device/Mode Display Explanation Refer to Section
C.1 Zonex and
Comex
Translation on
page 137.
302.
Fire Alarm
(point > 254)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa FIRE ALARM
+++ACC aaaa HIGH TEMPERATURE DETECTED
+++ACC aaaa AREA=aa POINT=pppp
h1rrlssssssaaaasFppppt
<header>[#aaaa|NriaaKApppp]
303.
Fire Alarm
(point > 254)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa FIRE ALARM
+++ACC aaaa WATER FLOW SENSOR
+++ACC aaaa WATER FLOW DETECTED
+++ACC aaaa AREA=aa POINT=pppp
h1rrlssssssaaaasFppppt
<header>[#aaaa|NriaaSApppp]
304.
Fire Cancel
(users > 254)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa FIRE CANCEL
+++ACC aaaa AREA=aa ID=iiii
h1rrlssssssaaaas\iiiit
<header>[#aaaa|Nriaa/idiiiiFC]
305.
Fire Missing
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa MISSING FIRE
+++ ACC aaaa AREA=a POINT=ppp
h1rrlssssssaaaasMspppt
<header>[#aaaa|NriaFYppp]
The POINT
(programmed with a
Fire Point code) in the
AREA in the second
line of the report is
missing.
1,
10.
306.
Fire Missing
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaa TROUBL FR z
h1rrlssssssaaaaGsssszt
<header>[#aaaa|NFTz]
2,
3,
9.
307.
Fire Missing
(points > 254)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa MISSING FIRE
+++ACC aaaa AREA=aa POINT=pppp
h1rrlssssssaaaasMppppt
<header>[#aaaa|NriaaFYpppp]
308.
Fire Restoral
(from Fire
Alarm)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa FIRE ALM RESTOR
+++ ACC aaaa AREA=a POINT=ppp
h1rrlssssssaaaaHsspppt
<header>[#aaaa|NriaFHppp]
309.
Fire
Restoral(from
Trouble/Missi
ng/Supervision
)
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa FIRE ALM RESTOR
+++ ACC aaaa AREA=a POINT=ppp
h1rrlssssssaaaaHsspppt
<header>[#aaaa|NriaFJppp]
310.
Fire Restoral
after Alarm
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaa RESTORAL FR z
h1rrlssssssaaaaHsssszt
<header>[#aaaa|NFRz]
2,
3,
9.
311.
Fire Restoral
after Alarm
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa FIRE RESTORAL
+++ ACC aaaa AREA=a POINT=ppp
h1rrlssssssaaaaHsspppt
<area not reported>
<header>[#aaaa|NriaFRppp]
The POINT
(programmed with a
Fire Point code) in the
AREA specified in the
second line of the
report was restored
after an alarm, trouble,
or missing condition.
1,
10.
312.
Fire Restore
after
Trouble/Missi
ng
Printer:
D6500 Mode:
SIA Mode:
dd/dd tt:tt Lxx ACC aaaa FIRE RESTORAL
+++ ACC aaaa AREA=a POINT=ppp
h1rrlssssssaaaaHsspppt
<header>[#aaaa|NriaFRppp]
The POINT
(programmed with a
Fire Point code) in the
AREA specified in the
second line of the
report was restored
after an alarm, trouble,
or missing condition.
1,
10.