3.1.31 SafeCom (Message Type p)
D6500 Byte Description
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... N-1 N
SafeCom Example
h p r r l A A A A E E E E
. . . data . . .
t
Table 36: SafeCom (Message Type p) Byte Description
# Title Description
1 Header Character (h)
Optional. Check with the computer automation software for compatibility.
2 Message Type
p
3-4 Receiver Number
Receiver gateway number from 01 to 99.
5 Line Card Number
Line number in the receiver gateway that sent the message.
6-9 Account Number
Four digits.
10-13 Event Code
Four digits.
14-(N-1) Data
Parameter data for event code.
N Trailer Character
Typically, HEX 14.
3.2 SIA Mode Messages
Use the SIA mode for central station monitoring.
3.2.1 Acron Super Fast (Message Type 9)
SIA Mode Description Acron Super Fast
Example
<LF><CRC><9><sequence#><receiver#><line#>[#aaaa|CCCCCCCC]<CR>
Table 37: Acron Super Fast (Message Type 9) Byte Description
Title Description
L
Standard line feed character.
CRC
Cyclical redundancy check number.
Message Type
9
sequence#
The message sequence number. The valid sequence number range is 0001 to 9999.
receiver#
The receiver gateway that sent the message. Valid digits are 01 to 99 for the
D6600/D6100.
line#
(Line/Group #)
The line number of the line in the receiver gateway that sent the message. Valid digits are 00
to 99. The receiver uses Line 0 (zero) for internal messages.
account#
The communicator's account number has four digits.
Figure 7: Message sent to printer
mm/ddshh:mmsLxxsACNsACCTsaaaa+++sACCsa
aaasCCCCsCCCC
For lines that are grouped, Gxx appears
instead of Lxx.
Table 38: Acron Super Fast (Message Type 9)
Printer Output
Characters Description
ACN Acron Super Fast format.
Lxx Line number.
Gxx Grouped line numbers.