GE GFK-1004B Network Router User Manual


 
5
5-12 TCP/IP Ethernet Communications User’s Manual – January 1996
GFK-1004B
PROM/software versions are incompatible, or station MAC address in soft switches does
not match downloaded configuration.
Table 5-4. Soft Switch Entry Utility Commands
Command Restrictions
bps
chbps
chdate (Not recommended if the PLC CPU is configured properly.)
chsosw (Not recommended if the PLC CPU is configured properly.)
chtime (Not recommended if the PLC CPU is configured properly.)
clear Limited to clear tally, clear log, and clear heap
clsosw (Not recommended if the PLC CPU is configured properly.)
date
help or ?
load
log
login
node
ok
restart
show Only task identifiers “b” and “c” are supported
sosw
stat Only task identifiers “b” and “c” are supported
tally Only task identifiers “b” and “c” are supported
time
Monitor Commands are not in italics. Modify Commands are shown in italics.
If the Soft Switch values are not defined or disagree with other evidence, the problem
must be satisfactorily resolved by one or more of the following actions:
1. Set the MAC address or IP address to the correct value via Logicmaster 90
Configurator.
2. If not configured via Logicmaster 90, use the CHSOSW Station Manager command
described in this chapter.
3. Adjust the GSM configuration for the Ethernet Interface.
4. Download the Ethernet Interface from the GSM.
Otherwise, you will be continually placed back into this utility after each restart. For
proper usage of the CHSOSW command, see the CHSOSW command description in this
chapter.
The Soft Switch Entry utility is exited by restarting the Ethernet Interface. This can be
accomplished by entering the RESTART or LOAD commands, pressing the Ethernet In-
terface Restart pushbutton, or by cycling power on the Series 90-70 PLC.