GE GFK-1004B Network Router User Manual


 
6
6-14 TCP/IP Ethernet Communications User’s Manual – January 1996
GFK-1004B
Table 6-10. Exception Log Event Codes - Continued
Log Event
Code Possible Cause and Resolution
Event “2”
System events
(Continued)
System Error: 3e7
“LAN I/F can’t init - check parms; running soft Sw util”
This error is caused by a request to release a buffer which is either still on a
queue or not on an even boundary. This is a catastrophic system software
error and should be reported to GE Fanuc - NA. The Ethernet Interface is
automatically restarted. If this error occurs within the first 60 seconds after
the Ethernet Interface was restarted or power cycled, the automatic restart
will force the Ethernet Interface into the Soft Switch Entry Utility.
System Error: bbbb
“Low battery signal”
This error occurs when the battery is disconnected or running low. Entry 3
indicates what type of transition has occurred:
0 Battery went from good to bad.
1 Battery went from bad to good (does not cause the STATUS LED to go
OFF).
System Error: cccc
“Module hardware fault”
This error occurs when the system detects an incorrect checksum in the
software or configuration data loaded into memory. This is a catastrophic
error. The Ethernet Interface is restarted with entry into the Software Load
Utility.
Entry 3 indicates the correct checksum value.
Entry 4 indicates the actual computed value.
Entry 5 indicates the internal range number within the software; range 0
indicates an error within the configuration data; Range ee indicates an
error within the copy of EEPROM data. Occurrence of this error should be
reported to GE Fanuc - NA.