REGENERATION POWER 155 allows drive to use regen 0: Off - 0 9-17
RIDE-THROUGH for control power 1: On *
REGENERATION RIDE- 156* maximum allowable 0.0 - 25 0.1 sec 2.0 9-17
THROUGH TIME ride-through time
AUTO-RESTART (MOTOR 157 "catch" a spinning motor 0: Off - 0 9-17
SPEED SEARCH) (forward or reverse) 1: After momentary
power failure
(ride-through)
2: After "ST" is
shorted to "CC"
3: Both 1 and 2
ELECTRONIC THERMAL 158 sets drive's overload to 10-100% or amps 1%/A 100 9-18
PROTECT LVL 1 protect motor
OVERLOAD REDUCTION 159 frequency at which drive's motor 0 - 30 0.1/0.01 Hz 30.0 9-18
START FREQ overload becomes speed sensitive
MOTOR 150% OVERLOAD 160 sets motor overload time 10 - 2400 10 sec 600 9-18
TIME LIMIT
OVERLOAD SELECTION 161 OL selection 0: Standard - 0 9-18
1: Soft stall on
2: Motor OL trip off
3: Soft stall on,
Motor OL trip off
STALL PROTECTION 162 Stall protection #1 0: On ** - 0 9-18
ENABLE 1: Off
STALL PROTECTION 163** sets current limit 10 - 215%/A 1 %/A 120 9-18
CURRENT LEVEL
UNDERVOLTAGE TRIP 164 Undervoltage detection can 0: Trip disabled - 0 9-18
SELECTION cause a warning or a trip 1: Trip enabled
UNDERVOLTAGE DETECT 165 Undervoltage detection time 0 - 10 0.01 sec 0.03 9-18
TIME
LOW CURRENT DETECT 166 Low current detection can 0: Trip disabled - 0 9-18
SELECTION cause a warning or a trip 1: Trip enabled
LOW CURRENT DETECT 167 Low current detection level 0 - 100% or amps 1%/A 0 9-19
LEVEL
LOW CURRENT 168 Low current detection time 0 - 255 1 sec 0 9-19
DETECTION TIME
OUTPUT SHORT-CIRCUIT 169 Output short-circuit detection 0: Standard - 0 9-19
DETECTION SELECT selection (OCL) 1: Less sensitive
short-circuit checki
2: Short-circuit check
at power up only
3: Combination of
1 and 2 above
8 - 14
GROUP:PROTECTION PARAMETERS (cont'd)
PARAMETER
DESCRIPTION
LIQUID CRYSTAL DISPLAY ADJUSTMENT
RANGE
ITEM
NO.
PAGE
NO.
DISPLAY
RESOLUTION
FACTORY
SETTING
Table continued on next page
*Item 156 is available only when Item 155 Adjustment Range option 1 is selected.
**Item 163 is available only when Item 162 Adjustment Range option 0 is selected.
Specifications
Precautions
Wiring