Toshiba H3 Power Supply User Manual


 
TOSHIBA
TOSLINE-F10/S20 268* TOSLINE-F10/TOSLINE-S20 0: Off - 0 9-23
MONITOR OUTPUT monitor output 1: Output frequency
2: Status
3: Output
frequency, status
4: Output current
5: Output
frequency,
output current
6: Status, output
current
7: Output
frequency,
status,
output current
8: Output voltage
9: Output
frequency,
output voltage
10:Output voltage,
status
11:Output
frequency,
output voltage,
status
12:Output voltage,
output current
13:Output voltage,
output current,
output frequency
14:Output voltage,
output current,
status
15:Output voltage,
output current,
output frequency,
status
TOSLINE-F10/S20 COMM 269 TOSLINE-F10 0: Data cleared - 0 9-23
ERROR MODE TOSLINE-S20 1: Data retained
communication error mode
RS485/12-BIT BINARY 270 RS485/12-bit binary input: bias 0: Off - 0 0 9-23
BIAS, GAIN and gain settings 1: On **
RS485/12-BIT BINARY 271** Point #1 setting signal 0 - 100% of 1% 0 9-23
POINT #1 Max. Out. Freq.
RS485/12-BIT BINARY 272** Output Hz desired with input 0 - Max. Out. Freq. 0.1/0.01 Hz 0.0 9-23
POINT #1 FREQ entered in Item 271
RS485/12-BIT BINARY 273** Point #2 setting signal 0 - 100% of 100% 100 9-23
POINT #2 Max. Out. Freq.
RS485/12-BIT BINARY 274** Output Hz desired with input 0 - Max. Out. Freq. 0.1/0.01 Hz 80.0 9-23
POINT #2 FREQ entered in Item 273
8 - 25
GROUP:COMMUNICATION SETTING PARAMETERS (cont'd)
PARAMETER
DESCRIPTION
LIQUID CRYSTAL DISPLAY ADJUSTMENT
RANGE
ITEM
NO.
PAGE
NO.
DISPLAY
RESOLUTION
FACTORY
SETTING
*Item 268 is available only when Item 264 Adjustment Range option 2 or 3 is selected.
**Items 271 - 274 are available only when Item 270 Adjustment Range option 1 is selected.
Cycle power after changing any parameter in GROUP:COMMUNICATION SETTING PARAMETERS.