Toshiba H3 Power Supply User Manual


 
TOSHIBA
9 - 26
Parameter Explanations (cont'd)
Item 283, PANEL OPERATION MODE SELECTION - Cycle power after changing this parameter.
This parameter limits what can be done via the keypad. Panel ESTOP in remote mode is ALWAYS valid.
The values entered here that are zero or are a power of two have one function assigned to them:
0: Keypad does nothing 1: Reset drive fault only
2: Monitor only
4:
ESTOP only
8:
Run/Stop only
16:
Read parameters only
32:
Change parameters only
The rest of the possible parameter values are combinations of the above.
Note: to "change parameters only", "read parameters only" must also be selected.
TO RESET AFTER "0" HAS BEEN PROGRAMMED IN ITEM 283:
1. Press four keys simultaneously: LOCAL/REMOTE, PRG, READ/WRITE, and
up arrow
2. Drive will display ENTER PASS NUMBER 0
3. Pass number is programmed in Item 284, PASS NUMBER. Enter pass number with
arrows and hit READ/WRT.
4. If entered correctly, PASS NUMBER ENTERED CORRECTLY will display briefly and Item
283 will be reset to a value of 63, allowing all keypad operations.
If ENTER PASS NUMBER doesn't appear after pressing the four keys, cycle power and try again.
Specifications
Precautions
Wiring
JumpersPanelKeypadParametersProgrammingServiceDimensionsIndex Inspection
Item 284, PASS NUMBER - Incorrect entry of the setting in this parameter prevents resetting
keypad lockout (Item 283 set to "0"). Item 284 is viewable through RS232 port.
Item 285, CPU VERSION - This is a read-only parameter. This manual is for the version 120 CPU. Version
120 added the following features to version 5101: input terminal functions 52,53, and 54; output terminal
functions 62 and 63; "RR" special input function #4; PID lower limit, peak voltage, peak current, and
calibration settings for AM/FM terminal functions; peak voltage and peak current monitor choices;
drooping control.
Item 286, ROM VERSION - This is a read-only parameter. "5120" is the default setting with a
version 120 CPU (230/460 volt drive). Application-specific option ROMs are available from Toshiba.
Item 287, EEPROM VERSION - This read-only parameter shows control board EEPROM version.
Item 288, INVERTER TYPEFORM - This read-only parameter identifies the drive model number:
Typeform Model Typeform Model
24 H3U2035
25 H3U2055 26 H3U2080
27 H3U2110 28 H3U2160
29 H3U2220 2A H3U2270
2B H3U2330
45 H3U4055 46 H3U4080
47 H3U4110 48 H3U4160
49 H3U4220 4A H3U4270
4B H3U4330 4C H3U4400
4D H3U4500 4E H3U4600
4F H3U4750 50 H3U410K
51 H3U412K 52 H3U415K
53 H3U420K 54 H3U425K
55 H3U430K