TOSHIBA
9 - 9
Parameter Explanations (cont'd)
The following are the functions that are realized when the appropriate drive terminal is shorted to "CC".
Program the desired code from the list below into items 44-55 (see). Contact the factory on how to
make a function active when the terminal is disconnected from "CC" (fail-safe).
Code Function
0 Reverse direction command (default for "R" terminal function)
1 Binary coding for number of preset speed desired. Value: +1 (default for "S1" terminal function)
2 Binary coding for number of preset speed desired. Value: +2 (default for "S2" terminal function)
3 Binary coding for number of preset speed desired. Value: +4 (default for "S3" terminal function)
4 Binary coding for number of preset speed desired. Value: +8 (default for "S4" terminal function)
5 Forward direction command (default for "F" terminal function)
6 Reset faults (momentary falling-edge trigger) (default for "RES" terminal function)
7 Drive enable (default for "ST" terminal function)
8 Jog (also need direction command). See items 108 and 109.
9 Select ACC1/DEC1 (open) or ACC2/DEC2 (closed to "CC")
10 Emergency stop. Also see item 151, EMERGENCY OFF MODE SELECTION.
11 DC injection. When outputting a frequency under DC INJECTION START FREQUENCY, short
terminal to "CC" to inject. Also see items 146, 147, and 148. Works in remote mode only.
12 Activate GROUP:FUNDAMENTAL PARAMETERS #1 (open) or GROUP:FUNDAMENTAL
PARAMETERS #2 (closed to "CC")
13 PID off (closed to "CC") or on (open)
14 Select Pattern Run #1
15 Select Pattern Run #2
16 Select Pattern Run #3
17 Select Pattern Run #4
18 Pattern Run continue signal
19 Pattern Run step signal
20 Jog forward (includes forward command). See items 108 and 109.
21 Jog reverse (includes reverse command). See items 108 and 109.
22 Bit #0 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/2048)
23 Bit #1 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/1024)
24 Bit #2 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/512)
25 Bit #3 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/256)
26 Bit #4 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/128)
27 Bit #5 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/64)
28 Bit #6 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/32)
29 Bit #7 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/16)
30 Bit #8 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/8)
31 Bit #9 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/4)
32 Bit #10 for binary speed reference (value of MAXIMUM OUTPUT FREQUENCY/2)
33 no function (use terminal to connect wires)
34 Motor operated pot: increase frequency reference
35 Motor operated pot: decrease frequency reference
36 Motor operated pot: clear frequency reference
37 Three wire control: NO momentary start push button
38 Three wire control: NO momentary stop push button. Contact factory for information on how to
realize stop with a NC contact.
40 Forward (open) or reverse (closed to "CC") command
41 Run (use in conjunction with 40 above)
42 Binary data write (use with 22-32 above). If no input terminal's function is set to "42", the drive
responds immediately to binary references commanded by changing data bits. If one of the input
terminal's function is set to "42", the drive responds to binary reference only when terminal is
closed to "CC". Binary reference is lost when power is cycled.
43 emulate LOCAL/REMOTE key
51 Drive/bypass switching signal
53 give "RR" priority over "IV" and "RX"
54 give "IV" priority over "RR" and "RX"