Programming Examples
Preset Speed Example
The following example uses "S1" and "S2" terminals to access three preset speeds of 11.0 Hz
(close "S1"-"CC"), 55.0 Hz (close "S2"-"CC"), and 33.7 Hz (close "S1" and "S2" to "CC"). "F"-"CC"
and "ST"-"CC" must be made on the drive's terminal strip. This example assumes drive is
defaulted to factory settings prior to when the following programming is done.
Group Parameter Value
UTILITY PARAMETERS BLIND FUNCTION SELECTION 1
UTILITY PARAMETERS FREQUENCY SETTING PARAMETERS BLIND 1
FREQUENCY SETTING PARAMETERS PRESET SPEED SELECTION 3
FREQUENCY SETTING PARAMETERS PRESET SPEED MODE ACTIVATION 0
FREQUENCY SETTING PARAMETERS PRESET SPEED #1 FREQUENCY 11
FREQUENCY SETTING PARAMETERS PRESET SPEED #1 OPERATING MODE 0
FREQUENCY SETTING PARAMETERS PRESET SPEED #2 FREQUENCY 55
FREQUENCY SETTING PARAMETERS PRESET SPEED #2 OPERATING MODE 0
FREQUENCY SETTING PARAMETERS PRESET SPEED #3 FREQUENCY 33.7
FREQUENCY SETTING PARAMETERS PRESET SPEED #3 OPERATING MODE 0
LOCAL LED must be off to run from terminal strip. See page 9-15 for parameter explanations.
Trim Pot Example
This example uses the "RX" terminal to trim a reference (i.e. a 4-20 mA input) +7/-5 Hz.
Group Parameter Value
UTILITY PARAMETERS BLIND FUNCTION SELECTION 1
UTILITY PARAMETERS FEEDBACK CONTROL PARAMETERS BLIND 1
UTILITY PARAMETERS FREQUENCY SETTING PARAMETERS BLIND 1
FEEDBACK PARAMETERS OVERRIDE CONTROL SELECTION 3
FREQUENCY SETTING PARAMETERS RX TERMINAL STANDARD OR ADJUSTABLE 1
FREQUENCY SETTING PARAMETERS RX REFERENCE SETTING POINT #1 0 %
FREQUENCY SETTING PARAMETERS RX REFERENCE POINT #1 FREQUENCY 7 HZ
FREQUENCY SETTING PARAMETERS RX REFERENCE SETTING POINT #2 100 %
FREQUENCY SETTING PARAMETERS RX REFERENCE POINT #2 FREQUENCY -5 HZ
Motor Operated Pot
The following programming allows a drive to emulate motor operated pot control. Momentarily
shorting "S1"-"CC" increases frequency reference. Momentarily shorting "S2"-"CC" decreases
frequency reference. Momentarily shorting "S3"-"CC" erases frequency reference. "F"-"CC" and
"ST"-"CC" must be made on the drive's terminal strip. This example assumes drive is defaulted to
factory settings prior to the following programming is done.
Group Parameter Value
UTILITY PARAMETERS BLIND FUNCTION SELECTION 1
UTILITY PARAMETERS TERMINAL SELECTION PARAMETERS BLIND 1
UTILITY PARAMETERS FREQUENCY SETTING PARAMETERS BLIND 1
TERMINAL SELECTION PARAMETERS INPUT TERMINAL SELECTION 1
TERMINAL SELECTION PARAMETERS "S1" INPUT TERMINAL FUNCTION 34
TERMINAL SELECTION PARAMETERS "S2" INPUT TERMINAL FUNCTION 35
TERMINAL SELECTION PARAMETERS "S3" INPUT TERMINAL FUNCTION 36
FREQUENCY SETTING PARAMETERS FREQUENCY PRIORITY SELECTION #1 5
The LOCAL LED must be off to run from terminal strip. See pages 9-7 and 9-13 for parameter
explanations.