Gateway 9415 Server User Manual


 
80
www.gateway.com
Power supply fans
Power supply fans are monitored and controlled by the power subsystem. A fan failure
(predicted or current) will show up in the IMM System Event Log (SEL) as a “Power Unit
0x01h” failure event and a GSM event will show up as “Power Unit Failure Detected.”
Power supply fans are not monitored by the mini-BMC, therefore no SEL or GSM events
will be reported with the mini-BMC configuration.
When a predicted or current fan failure is reported, the server must be opened to determine
which fan is having problems. LEDs on the power distribution board will indicate which
fan requires attention. The appropriate LED will blink to indicate a slow fan and light to
show a failed fan. The PS Fan 1 is on the left side of the module.
To replace a power supply fan:
1 Follow the instructions in “Preventing static electricity discharge” on page 41. Make
sure that you turn off the server, then unplug the power cord(s) and all other cables
connected to the server.
2 Follow the instructions in “Opening the server case” on page 42.
PS Fan 1 LED
PS Fan 2
LED