3 Follow the instructions in “Removing the power supply air duct” on page 49.
4 Disconnect the fan cable from the connector on the power distribution board.
5 Lift the fan from the power supply fan module assembly in the chassis.
6 Insert the replacement fan into the power supply fan module assembly.
7 Connect the fan cable to the connector on the power distribution board.
8 Follow the instructions in “Installing the power supply air duct” on page 50..
9 Follow the instructions in “Closing the server case” on page 44.
Important Make sure the arrows on top of the fans indicating airflow point to
the back of the chassis.The fan cable should exit the fan mudule
toward the back of the chassis.