TROUBLESHOOTING
1-201August 9, 2005
D SERIES CONTROLLER
TROUBLESHOOTING AND COMPONENT REPLACEMENT
K
a
a
aw
s
k
ERROR CODE W1005 Illegal center of gravity, default parameter is set.
Load mass value is set to a value other than zero, but the center of gravity is set to all
zeroes.
⇒
Enter the correct center of gravity value.
_____________________________________________________________________
ERROR CODE W1006 Incorrect load moment. Default parameter is set.
Load mass value and center of gravity are set, but the load moment of inertia is set to all
zeroes.
⇒
Set correct values for the load moment of inertia.
_____________________________________________________________________
ERROR CODE W1007 Application setting changed. Turn OFF & ON the control
power.
When application setting is changed, controller power must be cycled OFF and ON.
⇒
Cycle controller power OFF and ON.
_____________________________________________________________________
ERROR CODE W1008 Parameter changed. Turn OFF & ON the control power.
When parameters are changed, controller power must be cycled OFF and ON.
⇒
Cycle controller power OFF and ON.
_____________________________________________________________________
ERROR CODE W1009 Position envelope error of jtXX at last E-stop.
The error message is generated when an E-stop is applied and the position of the robot
is not within a range of the commanded position. The error deviation range is specified
in AUX 0503.
⇒
Before the error is reset, the operator must be aware of the robot’s position within the
work envelope.
_____________________________________________________________________