CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.2 Details of the buffer memory
(42)Temperature rise completion soak time setting (Un\G168)
Set the time for CH Temperature rise judgment flag (Un\G17 to Un\G20) ( Page 91, Section 3.4.2 (6)) to
be set to Within temperature rise completion range (1) after the completion of temperature rise.
(a) Setting range
The setting range is 0 to 3600 (min).
(b) Default value
The default value is set to 0 (min).
(43)PID continuation flag (Un\G169)
Set the operation status at the time when the mode has shifted from the operation mode to the setting mode
(Setting/operation mode instruction (Yn1) ON OFF).
For details on the relationship between this flag and the control status, refer to the following.
PID control: Page 170, Section 4.3 (6)
Temperature judgment: Page 87, Section 3.4.2 (3)
Alert judgment: Page 203, Section 4.12 (5)
(a) Setting range
0: Stop
1: Continue
(b) Default value
The default value is set to Stop (0).
(44)Heater disconnection compensation function selection (Un\G170)
Set whether to use the heater disconnection compensation function or not.
For details on the heater disconnection compensation function, refer to the following.
Page 266, Section 4.28 (3)
(a) Supported modules
Q64TCTTBWN
•Q64TCRTBWN
(b) Setting range
0: Not use the heater disconnection compensation function
1: Use the heater disconnection compensation function
(c) Default value
The default value is set to Not use the heater disconnection compensation function (0).