Mitsubishi Electronics Q64TCRTN Network Card User Manual


 
155
CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.2 Details of the buffer memory
(82)CH Simultaneous temperature rise dead time (Un\G732, Un\G748, Un\G764,
Un\G780)
Set Simultaneous temperature rise dead time (time taken for the temperature to start rising after the output is
turned on).
For details on the simultaneous temperature rise function, refer to the following.
Page 238, Section 4.20
(a) Setting range
The setting range is 0 to 3600 (s).
(b) Default value
The default values are set to 0 (s) in all channels.
This setting can not only be set manually but also be calculated automatically. Automatic calculation is performed when the
simultaneous temperature rise AT (auto tuning) or self-tuning (when the automatic calculation of the temperature rise
parameter is set) is normally completed.
(83)CH Simultaneous temperature rise AT mode selection (Un\G733, Un\G749,
Un\G765, Un\G781)
Select mode of the auto tuning.
For details on the auto tuning function, refer to the following.
Page 176, Section 4.6
For details on the simultaneous temperature rise function, refer to the following.
Page 238, Section 4.20
(a) Setting range
0: Select normal auto tuning
1: Simultaneous temperature rise AT
(b) Default value
The default values are set to Select normal auto tuning (0) in all channels.
This setting can be used with the setting of CH Auto tuning mode selection (Un\G184 to Un\G187). ( Page 136,
Section 3.4.2 (51))
If this setting is changed during the auto tuning, it is enabled in the next auto tuning.
Standard
Standard