4.12 Alert Function
(f) Setting method (alert mode and the set value (SV) to be referred)
Select one of the two types of set value (SV) described in Page 195, Section 4.12 (2) (a) by specifying an
alert mode.
When the alert judgment requires the value in CH Set value (SV) monitor (Un\G25 to Un\G28), set one
of the following values.
When the alert judgment requires the value in CH Set value (SV) setting (Un\G34, Un\G66, Un\G98,
Un\G130), set one of the following values.
Alert mode setting ( Page 204, Section 4.12 (7) (a))
Setting value Alert mode name
3 Upper limit deviation alert
4 Lower limit deviation alert
5 Upper lower limit deviation alert
6 Within-range alert
9 Upper limit deviation alert with standby
10 Lower limit deviation alert with standby
11 Upper lower limit deviation alert with standby
12 Upper limit deviation alert with standby (second time)
13 Lower limit deviation alert with standby (second time)
14 Upper lower limit deviation alert with standby (second time)
Alert mode setting ( Page 204, Section 4.12 (7) (a))
Setting value Alert mode name
15 Upper limit deviation alert (using the set value (SV))
16 Lower limit deviation alert (using the set value (SV))
17 Upper lower limit deviation alert (using the set value (SV))
18 Within-range alert (using the set value (SV))
19 Upper limit deviation alert with standby (using the set value (SV))
20 Lower limit deviation alert with standby (using the set value (SV))
21 Upper lower limit deviation alert with standby (using the set value (SV))
22 Upper limit deviation alert with standby (second time) (using the set value (SV))
23 Lower limit deviation alert with standby (second time) (using the set value (SV))
24 Upper lower limit deviation alert with standby (second time) (using the set value (SV))