Mitsubishi Electronics Q64TCRTN Network Card User Manual


 
97
CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.2 Details of the buffer memory
(a) Setting range of the Q64TCTTN, Q64TCTTBWN
The following table lists set values of CH Input range (Un\G32, Un\G64, Un\G96, Un\G128) and the
corresponding thermocouple types. The relationship between temperature unit and setting values is as follows.
Setting of CH Input range (Un\G32,
Un\G64, Un\G96, Un\G128)
Item
1 to 99 Thermocouple is used. (No input from
other analog modules (such as an A/D
converter module)) (1 to 199)
Output temperature unit is Celsius (°C).
100 to 199
Output temperature unit is Fahrenheit ( ).
200 to 299
Other analog modules (such as an A/D
converter module) are used. (200 to 299)
Unit is digit.
Thermocouple
type
Temperature
measurement
range
Celsius
(°C)/
Fahrenheit
( )/digit
Resolution
CH Input range
(Un\G32,
Un\G64, Un\G96,
Un\G128)
Auto-setting at input range change
*1
CH Upper limit
setting limiter
(Un\G55, Un\G87,
Un\G119,
Un\G151)
CH Lower limit
setting limiter
(Un\G56, Un\G88,
Un\G120,
Un\G152)
R
0 to 1700 °C 1 1 1700 0
0 to 3000 1 105 3000 0
K
-200.0 to 400.0 °C 0.1 38 4000 -2000
0.0 to 400.0 °C 0.1 36 4000 0
0 to 1300 °C 1
2
(Default value)
1300 0
0 to 500 °C 1 11 500 0
0.0 to 500.0 °C 0.1 40 5000 0
0 to 800 °C 1 12 800 0
0.0 to 800.0 °C 0.1 41 8000 0
0 to 1000 1 100 1000 0
0.0 to 1000.0 0.1 130 10000 0
0 to 2400 1 101 2400 0
J
0.0 to 400.0 °C 0.1 37 4000 0
0 to 500 °C 1 13 500 0
0.0 to 500.0 °C 0.1 42 5000 0
0 to 800 °C 1 14 800 0
0.0 to 800.0 °C 0.1 43 8000 0
0 to 1200 °C 1 3 1200 0
0 to 1000 1 102 1000 0
0.0 to 1000.0 0.1 131 10000 0
0 to 1600 1 103 1600 0
0 to 2100 1 104 2100 0