(40)Heater disconnection/output off-time current error detection delay count
(Un\G166)
Set the limit value for consecutive heater disconnection detections and output off-time current error detections so
that the errors exceeding the limit value triggers an alert judgment.
For details on the heater disconnection detection function, refer to the following.
Page 265, Section 4.28
For details on the output off-time current error detection function, refer to the following.
Page 269, Section 4.29
(a) Supported modules
•Q64TCTTBWN
•Q64TCRTBWN
(b) Setting range
The setting range is 3 to 255 (times).
(c) Default value
The default value is set to 3 (times).
(41)Temperature rise completion range setting (Un\G167)
Set the vertical range of the temperature rise completion range.
When the temperature process value (PV) meets the following conditions, the temperature rise is completed.
Set value (SV) - Temperature rise completion range Temperature process value (PV) Set value (SV) +
Temperature rise completion range
When CH Temperature process value (PV) (Un\G9 to Un\G12) enters the temperature rise judgment range,
CH Temperature rise judgment flag (Un\G17 to Un\G20) is set to Within temperature rise completion range (1).
(Set the time from the temperature rise completion to Within temperature rise completion range (1) in
Temperature rise completion soak time setting (Un\G168).)
(a) Setting range
When the temperature unit of the input range is °C: 1 to 10 (°C)
When the temperature unit of the input range is : 1 to 10 ( )
Other than above: 1 to 10 (%) of the full scale
(b) Default value
The default value is set to 1.
Common
Common
Temperature rise
completion range (+)
Set value (SV)
Temperature rise
completion range (-)
Temperature rise
judgment range
Setting value