Mitsubishi Electronics Q64TCRTN Network Card User Manual


 
39
CHAPTER 3 SPECIFICATIONS
3
3.1 Performance Specifications
*1 Calculate the accuracy in the following method (only when it is not affected by noise).
Accuracy (°C) = full scale × indication accuracy + cold junction temperature compensation accuracy
Accuracy at the input range of 38 (-200.0 to 400.0°C), the operating ambient temperature of 35°C, and the
temperature process value (PV) of 300°C
(Full scale) × (indication accuracy) + cold junction temperature compensation accuracy
= (400.0°C- (-200.0°C)) × (±0.007) + (±1.0°C)
= ± 5.2°C
*2 When the Q64TCTTBWN or Q64TCRTBWN is used, the device numbers of the I/O signals increase by 16 points
depending on how many free points the left-hand side slots have. Hence, as I/O signals are given as indicated below in
this manual, read them according to the module used.
When 0 is set as the start I/O number, Yn1 is assigned as follows.
When the Q64TCTTN or Q64TCRTN is used: Y1
When the Q64TCTTBWN or Q64TCRTBWN is used: Y11
For the noise immunity, dielectric withstand voltage, insulation resistance and others of the programmable controller
system which uses the Q64TCN, refer to the following.
QCPU User's Manual (Hardware Design, Maintenance and Inspection)
Transistor output
Output signal ON/OFF pulse
Rated load voltage 10 to 30VDC
Max. load current 0.1A/point, 0.4A/common
Max. inrush current 0.4A 10ms
Leakage current at OFF 0.1mA or less
Max. voltage drop at ON 1.0VDC (TYP) at 0.1A 2.5VDC (MAX) at 0.1A
Response time OFFON: 2ms or less, ONOFF: 2ms or less
Number of accesses to non-volatile memory
Max. 10
12
times
Insulation method
Between input terminal and programmable controller power supply: Transformer
insulation
Between input channels: Transformer insulation
Dielectric withstand voltage
Between input terminal and programmable controller power supply: 500VAC for
1 minute
Between input channels: 500VAC for 1 minute
Insulation resistance
Between input terminal and programmable controller power supply: 500VDC
20M or more
Between input channels: 500VDC 20M or more
Heater disconnection
detection specifications
Current sensor
Page 32, Section 2.1 (6)
Input accuracy Full scale × (±1.0%)
Number of alert delay 3 to 255
I/O occupied points
*2
16 points/slot
(I/O assignment: 16 intelligent points)
32 points/2 slots
(I/O assignment:
Vacancy for 16 points
+ 16 intelligent points)
Connection terminal 18-point terminal block Two 18-point terminal blocks
Applicable wire size
0.3mm
2
to 0.75mm
2
Applicable solderless terminal R1.25-3 (Crimping terminal with sleeve is unavailable.)
Internal current consumption 0.29A 0.33A
Weight 0.20kg 0.30kg
Outline dimensions 27.4(W)mm × 98(H)mm × 112(D)mm 55.2(W)mm × 98(H)mm × 112(D)mm
Item
Specifications
Q64TCTTN Q64TCRTN Q64TCTTBWN Q64TCRTBWN
Ex.
Ex.