ADIC Scalar 1000 Network Card User Manual


 
Event Codes and Actions 35
6-00020-02
SNC 5100
Figure 6: Detail of Event Log Listing From Service Port
Step 4. Check the listed Event Codes against the Event Code column of
Table 7 on page 35.
See Figure 6 to interpret the log listing.
Step 5. Read across Table 7 to the Action column to see the associated
Action number.
Step 6. Find the Action number in the Action column of Table 8 on
page 41.
Step 7. Complete the indicated MAP or action.
Step 8. To see additional log messages, follow the procedure Event Log
Dump on page 189.
Step 9. If there are no abnormal events, go to Perform Health Check on
page 46.
Table 7: Event Codes and Actions
Event
Code
Viewing
Level
1
Default
Trap
Threshold
Description
Action
2
Visual Observations
N.A. N.A. N.A. All LEDs are off 5
N.A. N.A. N.A. RDY LED not blinking once per
second after power has been on for
one minute
3
N.A. N.A. N.A. Temperature Warning LED on 4
N.A. N.A. N.A. Temperature Alarm LED on 4
N.A. N.A. N.A. SNC 5100 not responding 3