ADIC Scalar 1000 Network Card User Manual


 
SNC 5100
68 Power MAP
6-00020-02
Step 4. If obstructions are found, remove them and permit the SNC 5100 to
cool.
Step 5. If temperatures stabilize, exit this MAP.
Step 6. If no obstructions are found, or temperatures do not stabilize, check
the SNC 5100s Air Outlet for obstructions.
Step 7. If obstructions are found, remove them and permit the SNC 5100 to
cool.
Step 8. If temperatures stabilize, exit this MAP.
Step 9. If no obstructions are found, or temperatures do not stabilize,
replace the unit.
Proceed to Before Removing or Replacing the Unit on page 82.
Continue through Replacing the SNC 5100 on page 84.
Fan Speed is in Warning or Alarm Range
If you were directed to this MAP because of Trap Event Code 67, indicating
that the Fan is in Warning Range--replace the SNC 5100 at the next scheduled
maintenance.
If you were directed to this MAP because of Trap Event Code 68, indicating
that the Fan is in Alarm Range, Proceed to Before Removing or Replacing the
Unit on page 82.
Continue through Replacing the SNC 5100 on page 84.
Power MAP
Perform these steps if:
All LEDs are off
The SNC 5100 generates Trap Event Codes 59 or 60, indicating that the
Power is running in the Warning or Alarm Range. A string accompanying
a Trap Event will indicate which power supply is specifically involved.
Health Check generates a Trap Event Code 113, indicating that Power is
running in Warning or Alarm Range