Brocade MLX Series and Brocade NetIron XMR Hardware Installation Guide 355
53-1002373-02
Replacing a power supply
8
NOTE
A threshold value of 0 will not automatically shutdown a power supply due to failures.
For Syslog messages, please refer to Appendix A, Using Syslog in the Brocade MLX Series and
Brocade NetIron Family Configuration Guide.
Clearing power supply failure timestamps
Use the power-supply monitoring clear command to clear all collected failure timestamps for a
given power supply, or for all available power supplies.
To clear all collected failure timestamps for a power supply, enter the following command.
Brocade(config)# power-supply monitoring clear 1
This will clear all collected failure timestamps for the Power Supply # 1
Are you sure? (enter 'y' or 'n'): y
To clear all collected failure timestamps for all available power supplies, enter the following
command.
Brocade(config)# power-supply monitoring clear all
This will clear all collected failure timestamps for all available Power Supplies
Are you sure? (enter 'y' or 'n'): y
You are asked to verify this command by entering “yes” or “no.
Syntax: power-supply monitoring clear <decimal | all>]
By default, no power-supply monitoring is configured.
The <decimal> variable specifies a power supply number, The all keyword clears all available power
supplies.
Displaying power supply monitoring timestamps
To display timestamps for failures on any power supply, enter the following command.
Brocade# show power-supply-monitoring
PS-1 PS-2 PS-3 PS-4 PS-5 PS-6 PS-7 PS-8
1 ) 0 0 0 0 0 0 0 0
2 ) 0 0 0 0 0 0 0 0
3 ) 0 0 0 0 0 0 0 0
4 ) 0 0 0 0 0 0 0 0
5 ) 0 0 0 0 0 0 0 0
6 ) 0 0 0 0 0 0 0 0
7 ) 0 0 0 0 0 0 0 0
8 ) 0 0 0 0 0 0 0 0
9 ) 0 0 0 0 0 0 0 0
The show power-supply-monitoring command displays the last 32 recorded failure timestamps for
a power supply. The current configured power supply monitoring threshold value is also displayed
at the end of the output.
Syntax: show power-supply-monitoring