Underneath it another table shows which segment (H1 Link) of the Linking Device (FG-110
FF) is occupied and how many FF-H1 devices are connected under each segment.
Additional, for each available FF-H1 device the tag name is shown. So, the this table provide
a simple live list of the FF-H1 network. Please note that this list will be updated just be
clicking on “Fieldbus” again.
For each Linking Device up to 4 H1 Links (segments) are available. And under each
segment H1 Link up to 16 devices H1 are possible.
(In this example: Segment 1 (H1 Link) from Linking Device HSE_ DEVICE_1 is occupied by
two connected devices (H1 Device), flagged with a green check mark. The segments 2-4
(H1 Links) are free, flagged with red buttons.
Fig 4.3-3 Shows the actual configuration – Linking Device and occupancy of the 4 H1 Links (Segments)
4.3.4 <Diagnostics><Advanced>
The menu item <Diagnostics><Advanced> therefore shows two different menu items.
● Fieldbus Statistics
● Modbus Statistics.
4.3.4.1 <Diagnostics><Advanced><Fieldbus Statistics>
The menu item <Fieldbus Statistics> shows two different tables. The values specified apply
to the time since the program has been started or the latest <Reset count>.
The first table shows statistical data for each single occupied segment of the H1 Device.
● Messages Transmitted:
Assumption of all the transmitted messages for each occupied segment
● Good Messages received:
Assumption of the good messages received at each occupied segment.
● Total: Number of total retries.
● Live List Changes: Number of total live list changes
● Live List Pass Token Timeouts: Number of pass token timeouts; Under good
conditions it should be “0”