Mitsubishi Electronics Q64TCRTBWN Network Card User Manual


 
100
(b) Setting range of the Q64TCRTN, Q64TCRTBWN
The following table lists setting values of CH Input range (Un\G32, Un\G64, Un\G96, Un\G128) and the
corresponding platinum resistance thermometer types.
*1 When the input range is changed, the set values in some buffer memory areas are initialized automatically and return to
the default value (0).
( Page 101, Section 3.4.2 (12) (d))
*2 Same as the Q64TCTTN, Q64TCTTBWN
Remark
For the following control mode and channel, CH Input range (Un\G32, Un\G64, Un\G96, Un\G128) cannot be set to 201 to
205. If these values are set, a write data error (error code: 4
H
) occurs.
CH3 and CH4 in heating-cooling control (normal mode)
CH2 in mix control (normal mode)
Platinum
resistance
thermometer
type
Temperature
measurement
range
Celsius
(°C)/
Fahrenheit
( )/digit
Resolution
CH Input range
(Un\G32,
Un\G64, Un\G96,
Un\G128)
Auto-setting at input range change
*1
CH Upper limit
setting limiter
(Un\G55, Un\G87,
Un\G119,
Un\G151)
CH Lower limit
setting limiter
(Un\G56, Un\G88,
Un\G120,
Un\G152)
Pt100
-200.0 to 600.0 °C 0.1
7
(Default value)
6000 -2000
-200.0 to 200.0 °C 0.1 8 2000 -2000
-300 to 1100 1 141 1100 -300
-300.0 to 300.0 0.1 143 3000 -3000
JPt100
-200.0 to 500.0 °C 0.1 5 5000 -2000
-200.0 to 200.0 °C 0.1 6 2000 -2000
-300 to 900 1 140 900 -300
-300.0 to 300.0 0.1 142 3000 -3000
Input from other
analog modules
(0 to 4000)
*2
0 to 4000 digit 1 201 4000 0
Input from other
analog modules
(0 to 12000)
*2
0 to 12000 digit 1 202 12000 0
Input from other
analog modules
(0 to 16000)
*2
0 to 16000 digit 1 203 16000 0
Input from other
analog modules
(0 to 20000)
*2
0 to 20000 digit 1 204 20000 0
Input from other
analog modules
(0 to 32000)
*2
0 to 32000 digit 1 205 32000 0