Mitsubishi Electronics Q64TCRTBWN Network Card User Manual


 
151
CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.2 Details of the buffer memory
(72)CH Number of moving averaging (Un\G698 to Un\G701)
For each channel, set the number of moving averaging to be performed to temperature process values (PV).
For details on the moving averaging process to temperature process values (PV), refer to the following.
Page 191, Section 4.10
This setting is enabled only when Enable (0) is set to Moving Averaging Process Setting in the intelligent function
module switch setting. If Disable (1) is set to Moving Averaging Process Setting, this setting is ignored.
For details on the intelligent function module switch setting, refer to the following.
Page 299, Section 6.2
(a) Setting range
2 to 10 (times)
(b) Default value
2 (times) are set in all channels as default values.
(73)Cooling method setting (Un\G719)
Set the method for the cooling control in the heating-cooling control. Select the suitable cooling method for
cooling characteristics of devices.
The following figure shows the channel assignment of the buffer memory area.
For details on the cooling method setting function, refer to the following.
Page 258, Section 4.25
(a) Setting range
•0
H
: Air cooled
•1
H
: Water cooled
•2
H
: Linear
(b) Enablement of setting contents
Enable the setting contents by turning Setting change instruction (YnB) OFF ON OFF during the setting
mode (Setting/operation mode status (Xn1): OFF).
(c) Default value
The default value is set to Air cooled (0
H
).
Common
Heating-cooling
b15 b0
to to to to
b8 b7 b4 b3b11b12
CH4 CH3 CH2 CH1