Mitsubishi Electronics Q64TCRTBWN Network Card User Manual


 
379
APPENDICES
A
Appendix 3 When Using GX Developer and GX Configurator-TC
Appendix 3.1 GX Developer operation
(2) Intelligent function module switch setting
Configure the setting on "Switch setting" in "PLC parameter".
Parameter [PLC Parameter] [I/O assignment] Click .
Item Setting item
Switch 1
Control output HOLD/CLEAR setting
Set value Output setting
0 CLEAR
Other than 0 HOLD
Switch 2
Control mode selection
Set value
*1
Control mode Number of control loops
0000
H
Standard control Standard control 4 loops
0001
H
Heating-cooling control (normal mode) Heating-cooling control 2 loops
0002
H
Heating-cooling control (expanded mode)
*2
Heating-cooling control 4 loops
0003
H
Mix control (normal mode)
Heating-cooling control 1 loop
Standard control 2 loops
0004
H
Mix control (expanded mode)
*2
Heating-cooling control 2 loops
Standard control 2 loops
Switch 3
Function extension bit specification
Switch 4 0: Fixed (empty)
Switch 5 0: Fixed (empty)
Select "HEX.".
CH4CH3CH2CH1
H
b15b14b13b12b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
b0: Auto-setting at input range change
0: Disable
1: Enable
b1: Setting change rate limiter setting
0: Temperature rise/Temperature drop
batch setting
1: Temperature rise/Temperature drop
individual setting
Fixed to 0
Fixed
to 0
000000000000 0
b3: Moving averaging process setting
0: Enable
1: Disable