Mitsubishi Electronics Q64TCRTBWN Network Card User Manual


 
118
(27)CH MAN output setting (Un\G51, Un\G83, Un\G115, Un\G147)
This buffer memory area is used for setting the manipulated value (MV) in the MAN mode.
(a) How to shift the mode
Shift the mode by the following buffer memory area.
•CH AUTO/MAN mode shift (Un\G50, Un\G82, Un\G114, Un\G146) ( Page 117, Section 3.4.2 (26))
(b) Setting range
The setting range is different between the standard control and the heating-cooling control. ( Page 162,
Section 4.1)
In standard control: -50 to 1050 (-5.0 to 105.0%)
In heating-cooling control: -1050 to 1050 (-105.0 to 105.0%)
(c) Enablement of setting contents
Make sure the corresponding bits of MAN mode shift completion flag (Un\G30) has been set to 1 (ON) and
write a value in the MAN output setting.
A value that is written when MAN mode shift completion flag is OFF will be replaced with the manipulated value
(MV) calculated by PID operation by the system.
(d) Default value
The default values are set to 0 (0.0%) in all channels.
Common