Mitsubishi Electronics Q64TCRTBWN Network Card User Manual


 
146
*1 Indicates the values of CH Simultaneous temperature rise gradient data (Un\G731, Un\G747, Un\G763, Un\G779) and
CH Simultaneous temperature rise dead time (Un\G732, Un\G748, Un\G764, Un\G780).
This area is enabled only for the following channels.
CH1 to CH4 when the standard control is used
CH3 and CH4 when mix control (normal mode) or mix control (expanded mode) is used
For details on the simultaneous temperature rise function, refer to the following.
Page 238, Section 4.20
(68)CH Self-tuning setting (Un\G574, Un\G606, Un\G638, Un\G670)
Perform operation setting of self-tuning with this buffer memory area.
For details on the self-tuning function, refer to the following.
Page 223, Section 4.18
(a) Setting range
0: Do not run the ST
1: Starting ST (PID constants only)
2: Starting ST (Simultaneous temperature rise parameter only
*1
)
3: Starting ST (PID constants and simultaneous temperature rise parameter
*1
)
4: Starting ST plus vibration ST (PID constants only)
The simultaneous temperature rise parameter
*1
can be calculated during the self-tuning setting depending on
the setting.
*1 Indicates the values of CH Simultaneous temperature rise gradient data (Un\G731, Un\G747, Un\G763, Un\G779) and
CH Simultaneous temperature rise dead time (Un\G732, Un\G748, Un\G764, Un\G780) to be used in the
simultaneous temperature rise function.
For details on the simultaneous temperature rise function, refer to the following.
Page 238, Section 4.20
(b) Default value
The default values are set to Do not run the ST (0) in all channels.
This area is enabled only for the following channels.
CH1 to CH4 when the standard control is used
CH3 and CH4 when mix control (normal mode) or mix control (expanded mode) is used
Bit Flag name Description
b0
AT simultaneous temperature rise
parameter calculation completion
This flag is set to 1 (ON) when the simultaneous temperature rise
parameter
*1
is calculated by simultaneous temperature rise AT.
b1
AT simultaneous temperature rise
parameter calculation error status
This flag is set to 1 (ON) when the simultaneous temperature rise
parameter
*1
cannot be calculated by simultaneous temperature rise
AT.
b2
Simultaneous temperature rise AT
disable status
This flag is set to 1 (ON) when the simultaneous temperature rise
AT cannot be performed.
b3 to b15 (fixed to 0) (Unused)
Standard