268
(4) To clear the disconnection detection status
Disconnection detection is disabled by restoring the disconnection status and turning CH Heater disconnection
detection (b12 of Un\G5 to Un\G8) from 1 (ON) to 0 (OFF). ( Page 87, Section 3.4.2 (3))
The timing when a heater turns on differs depending on the setting for the following buffer memory areas.
Buffer memory area name
Buffer memory address
Reference
CH1 CH2 CH3 CH4
CH Control output cycle setting
Un\G47 Un\G79 Un\G111 Un\G143
Page 114, Section 3.4.2 (23)
CH
Heating control output cycle setting
Un\G47 Un\G79 Un\G111 Un\G143
CH
Cooling control output cycle setting
Un\G722 Un\G738 Un\G754 Un\G770