Mitsubishi Electronics Q64TCRTBWN Network Card User Manual


 
157
CHAPTER 3 SPECIFICATIONS
3
3.4 Buffer Memory Assignment
3.4.2 Details of the buffer memory
(85)CH Setting change rate limiter time unit setting (Un\G735, Un\G751, Un\G767,
Un\G783)
Set the time unit of setting change rate limiter.
For details on the setting change rate limiter time unit setting function, refer to the following.
Page 190, Section 4.9
(a) Setting range
0 (Not use time unit setting)
1 to 3600 (1 to 3600s)
A setting of 0 results in the same operation with the setting of 60 corresponding to one minute.
(b) Enablement of setting contents
Enable the setting contents by turning Setting change instruction (YnB) OFF ON OFF during the setting
mode (Setting/operation mode status (Xn1): OFF).
(c) Default value
The default values are set to 0 (Not use time unit setting) in all channels.
Remark
When 0 is set, the Q64TCN operation is the same as the case when 60, a variation per minute, is set.
Common