Mitsubishi Electronics Q64TCRTBWN Network Card User Manual


 
134
(48)Resolution of the manipulated value for output with another analog module
(Un\G181)
Set the resolution of the following buffer memory areas. ( Page 89, Section 3.4.2 (5))
•CH Manipulated value (MV) (Un\G13 to Un\G16)
•CH Manipulated value for heating (MVh) (Un\G13 to Un\G16)
•CH Manipulated value for cooling (MVc) (Un\G704 to Un\G707)
For details, refer to the following.
Page 221, Section 4.16 (2)
(a) Setting range
0: 0 to 4000
1: 0 to 12000
2: 0 to 16000
3: 0 to 20000
The manipulated value (MV) reflecting the resolution is stored in the following buffer memory areas.
( Page 133, Section 3.4.2 (47))
•CH Manipulated value (MV) for output with another analog module (Un\G177 to Un\G180)
•CH Manipulated value of heating (MVh) for output with another analog module (Un/G177 to Un\G180)
•CH Manipulated value of cooling (MVc) for output with another analog module (Un\G708 to Un\G711)
(b) Enablement of setting contents
Enable the setting contents by turning Setting change instruction (YnB) OFF ON OFF during the setting
mode (Setting/operation mode status (Xn1): OFF).
(c) Default value
The default value is set to 0 to 4000 (0).
Common