CHAPTER 6 VARIOUS SETTINGS
6
6.2 Switch Setting
6.2 Switch Setting
Configure settings such as the output setting at CPU stop error and the control mode selection which are used in each
channel.
(1) Setting method
Open the "Switch Setting" window.
Project window [Intelligent Function Module] Module name [Switch Setting]
*1 Immediately after the control mode selection is changed, a set value discrepancy error (error code: 001E
H
) occurs. To
clear the set value discrepancy error, turn off, on, and off E
2
PROM backup instruction (Yn8).
Item Description Set value Reference
Output Setting at
CPU Stop Error
Set whether to hold or clear the transistor output status
when a CPU stop error occurs or when a CPU module is
switched from RUN to STOP.
• 0: CLEAR (default value)
•1: HOLD
Page 165,
Section 4.2
Control Mode
Selection
*1
Set the control mode.
• 0: Standard Control
• 1: Heating/Cooling Control (Normal Mode)
• 2: Heating/Cooling Control (Expanded
Mode)
• 3: Mix Control (Normal Mode)
• 4: Mix Control (Expanded Mode)
Page 162,
Section 4.1
Auto-setting at
Input Range
Change
Set this item to change data of the related buffer
memory automatically when the input range is changed
so that an error which is out of the setting does not
occur.
• 0: Disable
• 1: Enable
Page 220,
Section 4.15
Setting Change
Rate Limiter
Select "batch" setting or "individual" setting for the
setting change rate limiter at temperature rise and drop .
• 0: Temperature Rise/Temperature Drop
Batch Setting
• 1: Temperature Rise/Temperature Drop
Individual Setting
Page 190,
Section 4.9
Moving
Averaging
Process Setting
Set whether to enable or disable the moving averaging
process.
• 0: Enable
• 1: Disable
Page 191,
Section 4.10