Mitsubishi Electronics Q64TCRTBWN Network Card User Manual


 
234
(1) The number of timing divided and upper limit output limiter
Set the number of timing to be divided (setting in Peak current suppression control group setting (Un\G784) in the
setting mode (Setting/operation mode status (Xn1): off). The setting is enabled by turning off, on, and off Setting
change instruction (YnB). At the time when the setting is enabled, the following buffer memory area is
automatically set according to the number of timing divided.
•CH Upper limit output limiter (Un\G42, Un\G74, Un\G106, Un\G138)( Page 110, Section 3.4.2 (19))
The following table lists the setting details.
The following buffer memory area is set to 0.
•CH Lower limit output limiter (Un\G43, Un\G75, Un\G107, Un\G139) ( Page 110, Section 3.4.2 (19))
When using this function, set the control output cycles for target channels to the same value. Even if the following buffer
memory area setting is different by each channel, an error does not occur.
•CH Control output cycle setting (Un\G47, Un\G79, Un\G111, Un\G143)
( Page 114, Section 3.4.2 (23))
The module operates according to the value (%) of CH Upper limit output limiter (Un\G42, Un\G74, Un\G106, Un\G138)
automatically set when this function is used.
Ex.
Timing chart of when timing is divided into four timing
The no. of timing divided CH Upper limit output limiter (Un\G42, Un\G74, Un\G106, Un\G138)
2 500(50.0%)
3 333(33.3%)
4 250(25.0%)
Setting/operation mode instruction (Yn1)
Setting/operation mode status (Xn1)
Setting change instruction (YnB)
Setting change completion flag (XnB)
Peak current suppression control
group setting (Un\G784)
CH Upper output limiter
(Un\G42, Un\G74, Un\G106, Un\G138)
Executed in a sequence program
Executed by the Q64TCN
ON
ON
0
250 (25.0%)
(Automatic
storing)
0000H 4321H
OFF
ON
(Change the automatically-
calculated result if needed.)
OFF
OFF
ON
OFF