12
TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 38
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3100
• The number of modules actually
mounted is different from that is set in
Network parameter for CC-Link IE
Controller Network.
• The start I/O number of the module
actually mounted is different from that
is set in Network parameter for
CCLink IE Controller Network.
• Some data in the parameters are not
supported.
• The station type for a CC-Link IE
Controller Network has been
changed while the power is ON.
(RESET RUN is required to
change the station type.)
• Check the setting in Network
parameter and actual mounting
status, and if they differ, correct either
the setting or mounting status so that
they become the same. If the
parameter setting is corrected, write
Network parameter to the CPU
module.
• If an error occurs even after
correction, a hardware failure is
considered. (Please consult your
local Mitsubishi representative.)
QS
• The number of modules actually
mounted is different from that is set in
Network parameter for MELSECNET/
H.
• The start I/O number of the module .
actually mounted is different from
thatis set in Network parameter for
MELSECNET/H.
• Some data in the parameters are not
supported.
• The station type for a MELSECNET/H
has been changed while the power is
ON.
(RESET RUN is required to
change the station type.)
• The mode switches of MELSECNET/
H module
*1
are out of the setting
range.
• Check the setting in Network
parameter and actual mounting
status, and if they differ, correct either
the setting or mounting status so that
they become the same. If the
parameter setting is corrected, write
Network parameter to the CPU
module.
• If an error occurs even after
correction, a hardware failure is
considered. (Please consult your
local Mitsubishi representative.)
• Set the mode switches of
MELSECNET/H module
*1
within the
setting range.
QS
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*1 This applies when the serial number (first five digits) of the MELSECNET/H module is "08102" or later.
*2 This applies when the serial number (first five digits) of the CPU module is "10031" or earlier.
*3 This applies when the serial number (first five digits) of the CPU module is "13042" or later.