Mitsubishi Electronics QSPCU Personal Computer User Manual


 
12
TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 40
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3101
The refresh parameter for CC-Link IE
Controller Network is out of the setting
range.
Check the setting in Network parameter
and actual mounting status, and if they
differ, correct either the setting or
mounting status so that they become
the same. If the parameter setting is
corrected, write Network parameter to
the CPU module.
QS
• The refresh parameter for CC-Link IE
Field Network is out of the setting
range.
• The refresh parameter for CC-Link IE
Field Network is overlapped with the
refresh parameter or the I/O
assignment setting for other
networks.
• The start I/O number of the module
actually mounted is different from that
is set in Network parameter.
• The refresh parameter for
MELSECNET/H is out of the setting
range.
3102
• The network module detected an
error in Network parameter.
• The MELSECNET/H inherent
parameter setting is incorrect.
• Correct the parameter setting and
write Network parameter to the CPU.
• If an error occurs even after
correction, a hardware failure is
considered. (Please consult your
local Mitsubishi representative.)
QS
3103
• The number of modules actually
mounted is different from that is set in
Network parameter for Ethernet.
• The start I/O number of the module
actually mounted is different from that
is set in Network parameter for
Ethernet.
• Check the setting in Network
parameter and actual mounting
status, and if they differ, correct either
the setting or mounting status so that
they become the same. If the
parameter setting is corrected, write
Network parameter to the CPU
module.
• If an error occurs even after
correction, a hardware failure is
considered. (Please consult your
local Mitsubishi representative.)
QS
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*1 This applies when the serial number (first five digits) of the MELSECNET/H module is "08102" or later.
*2 This applies when the serial number (first five digits) of the CPU module is "10031" or earlier.
*3 This applies when the serial number (first five digits) of the CPU module is "13042" or later.