12
TROUBLESHOOTING
12.3 Error Code List
12.3.5 Error code list (3000 to 3999)
12 - 42
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
3104
• The same network number is used for
Ethernet, CC-Link IE Controller
Network, and MELSECNET/H.
• The network number, station number,
and/or group number set in Network
parameter are out of the setting
range.
• The specified I/O number is outside
the range of the used CPU module.
• The Ethernet inherent parameter
setting is incorrect.
• Correct the parameter setting and
write Network parameter to the CPU
module.
• If an error occurs even after
correction, a hardware failure is
considered. (Please consult your
local Mitsubishi representative.)
QS
3105
• Though the number of CC-Link
modules set in the network
parameters is one or more, the
number of actually mounted modules
is zero.
• The start I/O number in the common
parameters is different from that of
the actually mounted module.
• The station type of the CC-Link
module count setting parameters is
different from that of the actually
mounted station.
• Correct and write the network
parameters.
• If the error occurs after correction, it
suggests a hardware fault. (Please
consult your local Mitsubishi
representative.)
QS
3106
• The network refresh parameter for
CC-Link is out of range.
• Although the safety remote station set
in the network parameter does not
support the safety data monitoring
time, it is set for the station.
• The refresh parameter for CC-Link IE
Field Network is overlapped with the
refresh parameter or the I/O
assignment setting for other
networks.
• Check the [Model name] and [Module
technical version] of the safety
remote station settings, or delete the
setting of the safety data monitoring
time.
• Correct and write the network
parameters.
• If the error occurs after correction, it
suggests a hardware fault. (Please
consult your local Mitsubishi
representative.)
QS
The safety data monitoring time has
been set.
Delete the setting of the safety data
monitoring time.
QS
*2
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*1 This applies when the serial number (first five digits) of the MELSECNET/H module is "08102" or later.
*2 This applies when the serial number (first five digits) of the CPU module is "10031" or earlier.
*3 This applies when the serial number (first five digits) of the CPU module is "13042" or later.