12
TROUBLESHOOTING
12.3 Error Code List
12.3.8 Error code list (8000 to 9000)
12 - 64
9
EMC AND LOW
VOLTAGE
DIRECTIVES
10
LOADING AND
INSTALLATION
11
MAINTENANCE AND
INSPECTION
12
TROUBLESHOOTING APPENDICES INDEX
8426
Safety monitoring timeout error (A
timeout error occurred during safety
communication.)
• Check that the following operations
are not performed.
1) Switching the operation mode
2) Writing the program memory to
ROM
3) Registration/change of the CPU
access password
4) Initialization of PLC memory
5) Monitoring, diagnostics
(If executed, this error may occur due
to the increase of the interval
between data communications of CC-
Link IE Field.)
• Set the larger value for the safety
refresh monitoring time. Or set the
smaller value for the transmission
interval monitoring time.
• It may be malfunction due to noise.
Check the soundness of transmission
path by performing the CC-Link IE
Field Network diagnostics. Check the
distance between power lines and
communication cables, and the
installation status of each device as
well.
QS
*3
8430
Safety station reception data error
(Incorrect data is received.)
It may be malfunction due to noise.
Check the soundness of transmission
path by performing the CC-Link IE Field
Network diagnostics. Check the
distance between power lines and
communication cables, and the
installation status of each device as
well.
QS
*3
8431
8432
8440
Safety connection setting error
(Incorrect CID is received.)
Check that safety connection is
correctly set for own station.
QS
*3
9000
Annunciator (F) was set ON
(**** in the error message indicates the
detected annunciator number.)
Read the individual information of the
error using the GX Developer, and
check the program corresponding to the
numerical value (annunciator number).
QS
Error
Code
(SD0)
Error Contents and Cause Corrective Action
Corresponding
CPU
*3 This applies when the serial number (first five digits) of the CPU module is "13042" or later.