5 - 1
5.1 Specifications
5
POWER SUPPLY MODULE
CHAPTER5 POWER SUPPLY MODULE
This section describes the specifications of the power supply modules applicable for the
programmable controller system and how to select the most suitable module.
5.1 Specifications
Table5.1 shows the specifications of the power supply modules.
Table5.1 Power supply module specifications
Item
Performance Specifications
QS061P-A1 QS061P-A2
Base loading position QS series power supply module loading slot
Applicable base unit QS034B
Input power supply
100 to 120VAC
(85 to 132VAC)
200 to 240VAC
(170 to 264VAC)
Input frequency
50/60Hz 5%
Input voltage distortion ratio
Within 5% ( Section 5.2)
Max. input apparent power 125VA
Inrush current
20A, 8ms or less
*4
Rated output
current
5VDC 6A
Overcurrent
protection
*1
5VDC 6.6A or more
Overvoltage
protection
*2
5VDC 5.5 to 6.5V
Efficiency 70% or more
Allowable momentary power
failure period
*3
Within 20ms
Withstand voltage
1780VAC rms/3 cycles between all inputs
and LG and all outputs and FG (2000 m
(6562 ft.) above sea level)
2830VAC rms/3 cycles between all inputs
and LG and all outputs and FG
(2000 m (6562 ft.) above sea level)
Insulation resistance
10M or higher (500VDC insulation resistance tester) between:
• all inputs and LG and all outputs and FG
• all inputs and LG
• all outputs and FG
Noise immunity
• Noise voltage 1500Vp-p, noise width 1 s, noise frequency 25 to 60Hz (noise
simulator condition)
• Noise voltage IEC61000-4-4: 2kV
Operation indication LED indication (Normal: On (green), Error: Off)
Fuse Built-in (Unchangeable by user)
+10%
-15%
+10%
-15%