Form Heading Description Example
Power Factor Phasepower factor. N/A
Environmental Sensors Information
Type (Name) Type ofthesensor.
Temperature-
Internal
Current information displays the actual alarm state of the current level based on the configured
thresholds when available. The alarm state can have one of the following values:
• Tripped - when hardware overcurrent protection is tripped
• High Critical - when the value is greater than the high critical threshold
• High Warning - when the value is greater than the high warning threshold and less
than the high critical threshold
• Low Warning - when the value is greater than the low critical threshold and less than
the low warning threshold
• Low Critical - when the value is less than the low critical threshold
Voltage, Power Factor and Power Consumption display the Estimated or Measured value.
NOTE: Somepower devicesdonothavethecapabilitytoreadtherealinput voltage/power factor using proper
voltage/power factor sensors;in thiscasethe valuesareconfigurable.
When recorded maximum value is provided by the PDU, it is shown in the same row of the
actual value.
To view and reset IPDU information:
1. Select Applications - IPDU Power Mgmt. - View IPDUs Info. The View IPDUs Info screen
appears.
2. To clear the stored maximum values, click the Clear or Reset button.
Applications - IPDU Power Mgmt. - Configuration
An administrator can select Expert - Applications - IPDU Power Mgmt. - Configuration to
configure each configured IPDU.
NOTE: The operatingparametersmaydiffer dependingonthemakeandmodelofIPDU.
Chapter 6: Applications 59